Installation
Communications Wiring
Terminating the Communications
Link
To ensure reliable communications, terminate the last device on a POWERLOGIC
communications link. The illustration below shows MCT-485 terminator placement
when the final device on the link is a POWERLOGIC device. If the last device is a
Sepam™ Series 80, see page 60 and page 62 for termination instructions.
If a communications link contains only a single device, it must be terminated. If a link
contains multiple devices, as in the illustration on page 74, only the last device must
be terminated.
One pair of terminating resistors is required at each end of an RS485 4-wire daisy
chain. This can be accomplished by setting the movable jumpers on the ACE959
communications interface, the switches on Black Box converter IC109A-R2, or, for
series 2000 circuit monitors, using a Multipoint Communication Adapter MCT-485.
For series 4000 circuit monitors and series 600 power meters with screw-type
terminals, use an MCTAS-485 (or an MCT-485 with a terminal block). Refer to the
instruction bulletin for the specific device for more details.
Integral jumpers on the Sepam™ ACE modules provide the ability to
select terminating resistance (Rc) or not (’Rc). See the respective ACE
module in this manual for details.
IN+
SHLD
OUT-
OUT+
IN-
MCT485
Terminator
(Class 3090)
Terminal
Block
POWERLOGIC Device
(Last Device on Link)
RS485
Terminals
Terminating a device using an MCT-485 and a terminal block
Belden 8723 Cable