62
© 2007 Schneider Electric. All Rights Reserved.
1
63230-216-229-B1
Installation
ACE937 Fiber Optic Interface
Function
PE50024
The ACE937 interface connects Sepam™ to a fiber optic communication star
system. A CCA 612 cord connects this remote module to the Sepam™ base unit.
Characteristics
ACE937 Module
Weight 0.1 kg (0.22 lb)
Assembly On symmetrical DIN rail
Power supply Supplied by Sepam™
Operating temperature –25°C to +70°C (–13°F to +158°F)
ACE937 fiber optic connection interface. Environmental characteristics Same characteristics as Sepam™ base units
Fiber Optic Interface
Fiber type Graded-index multimode silica
Wavelength 820 nm (invisible infra-red)
Type of connector ST (BFOC bayonet fiber optic connector)
CAUTION
Fiber Optic
Diameter
(µm)
Numerical
Aperture (NA)
Maximum
Attenuatio
n (dBm/km)
Minimum Optical
Power Available
(dBm)
Maximum
Fiber Length
POTENTIAL EYE INJURY
b Never look directly into the end of a fiber
optic cable
Failure to follow this instruction can cause
serious injury.
50/125 0.2 2.7 5.6 700 m (2300 ft)
62.5/125 0.275 3.2 9.4 1800 m (5900 ft)
100/140 0.3 4 14.9 2800 m (9200 ft)
200 (HCS) 0.37 6 19.2 2600 m (8500 ft)
The maximum length is calculated with:
b Minimum optical power available
b Maximum fiber attenuation
b Losses in two ST connectors: 0.6 dBm
b Optical power margin: 3 dBm (according to IEC 60870 standard)
Example for a 62.5/125 µm fiber
Lmax = (9.4 - 3 - 0.6)/3.2 = 1.8 km (1.12 mi)
Description and Dimensions
DE80037
RJ45 socket connects the interface to the base unit with a CCA612 cord
1 The link activity LED flashes when active communication occurs (sending or
receiving in progress)
2 Receive (Rx), female ST type connector (Sepam™ receiving)
3 Transmit (Tx), female ST type connector (Sepam™ sending)
(1) 70 mm (2.8 in) with CCA612 cord connected.
DE51666
Connection
b The sending and receiving fiber optic fibers must be equipped with male ST
type connectors
b Fiber optics screw-locked to Rx and Tx connectors
Use a CCA612 cable (length = 9.8 ft, or 3 m, green fittings) to connect the interface
to on the base unit.
in.
(mm)
3.46
(88)
2.83
(72)
(30)
(1)
1.18
C
C
Zobrazit stránku 67