17
1
© 2007 Schneider Electric. All Rights Reserved.
63230-216-229-B1
Installation
Base Unit
Connection
Items located on the rear panel are:
1 Base unit
2 Eight spring clips (four top, four bottom)
3 Red LED: Sepam™ unavailable
4 Green LED: Sepam™ on
5 Gasket
20-pin connector for:
b 24 V DC to 250 V DC auxiliary supply
b five relay outputs
Connector for 3 phase current Ia, Ib, Ic inputs
Sepam™ T87, M87, M88, G87, G88: connector
for 3-phase current I'a, I'b, I'c inputs
b Sepam™ B83: connector for
v 3-phase voltage V'an, V'bn, V'cn inputs
v 1 residual voltage V’r input (see page 25)
b Sepam™ C86: connector for capacitor
unbalance current inputs (see page 29)
Communication port 1
Communication port 2
Remote module connection port 1
Remote module connection port 2
20-pin connector for:
b 3 phase voltage Van, Vbn, Vcn inputs
b 1 residual voltage Vr input
b 2 residual current Ir, I'r inputs
Spare port
Rear Panel Description
DE51781
Connector for first MES120 input/output module.
Connector for second MES120 input/output module.
Connector for third MES120 input/output module.
Functional ground.
Connection Characteristics
Connector Type Reference Wiring
, Screw type CCA620
Wiring with no fittings:
b 1 wire with max. cross-section 0.2 to 2.5 mm² ( AWG
24-12) or 2 wires with max. cross-section 0.2 to 1 mm²
(
AWG 24-16)
b Stripped length: 8 to 10 mm (0.31 to 0.39 in)
Wiring with fittings:
b Recommended wiring with Telemecanique fittings:
v DZ5CE015D for 1 x 1.5 mm² wire (AWG 16)
v DZ5CE025D for 1 x 2.5 mm² wire (AWG 12)
v AZ5DE010D for 2 x 1 mm² wires (AWG 18)
b Tube length: 8.2 mm (0.32 in)
b Stripped length: 8 mm (0.31 in)
6.35 mm (0.25 in) ring lugs CCA622 b 6.35 mm ring or spade lugs (0.25 in) (1/4")
b Maximum wire cross-section of 0.2 to 2.5 m
(
AWG 24-12)
b Stripped length: 6 mm (0.23 in)
b Use an appropriate tool to crimp the lugs on the wires
b Maximum of 2 ring or spade lugs per terminal
b Tightening torque: 6.1 - 8.8 in-lb (0.7 to 1 Nm)
, 4 mm (0.15 in) ring lugs CCA630 or CCA634, to connect 1A or 5A CTs 1.5 to 6 mm² (AWG 16-10)
RJ45 plug CCA671, to connect 3 LPCT sensors Integrated with LPCT sensor
, Green RJ45 plug CCA612
, Black RJ45 plug CCA770: L = 2 ft (0.6 m)
CCA772: L = 6.6 ft (2 m)
CCA774: L = 13.1 ft (4 m)
CCA785 for MCS025 module: L = 6.6 ft (2 m)
DE51845
Functional ground
Ring lug Grounding braid, to be connected to cubicle ground:
b Flat copper braid with cross-section u 9 mm²
(> AWG 8)
b Maximum length: 11.8 in (300 mm)
A
B1
B2
C1
C2
D1
D2
E
F
H1
H2
H3
t