9563230-216-229-B1
2
© 2007 Schneider Electric. All Rights Reserved.
Use
SFT2841 Set Up and Operating
Software
Using the Software
Disconnected Mode Connected Mode
Sepam™ Parameter and Protection Setting
When you use SFT2841 software, setting Sepam™
parameters and protection consists of preparing the
Sepam™ file that contains the characteristics
pertaining to your application. This file loads into
Sepam™ during commissioning.
Precaution
When using a laptop, remember the risks involving static electricity. The customary
precaution consists of discharging in contact with an grounded metal frame before
physically connecting the CCA783 cord.
Plugging into Sepam™
1 Plug the 9-pin connector (SUB-D type) into one of the PC communication ports.
2 Configure the PC communication port via the "Communication port" function in
the "Options" menu.
3 Plug the 6-pin connector into the connector (round MiniDin type) situated behind
the blanking plate on the front panel of Sepam™ or the DSM303 module.
Connection to Sepam™
There are two possible setup connections between SFT2841 and Sepam™:
b "Connection" function in the "File" menu
b choosing "connect to the Sepam™" at SFT2841 start-up
Once the connection with Sepam™ is established, "Connected" appears in the
status bar, and you can access the Sepam™ connection window in the work zone.
User Identification
The window intended for the entry of the 4-digit password is activated:
b via the "General characteristics" tab, "Passwords" button
b via the "Identification" function in the "Sepam™" menu
The "Return to Operating mode" function in the "Passwords" tab withdraws access
rights to the parameter and protection setting mode
Loading Parameters and Protection Settings
Parameter and protection setting files may only be loaded in the connected Sepam™
in Parameter setting mode.
Once the connection has been established, the procedure for loading a parameter
and protection setting file is as follows:
1 Activate the "Load Sepam™" function in the "Sepam™" menu
2 Select the file (*.S80, *.S81, *.S82, *.S84, *.T81, *.T82, *.T87, *.M81, *.M87,
*.M88, *.G82, *.G87, *.G88, *.B80, *.B83, or *.C86) according to the type of
application) which contains the data to be loaded.
Return to Factory Settings
This operation is only possible in Parameter setting mode in the "Sepam™" menu.
All Sepam™ general settings, protection settings and the control matrix return to their
default values. The return to factory settings does not erase the logic equations. The
logic equation editor must be used to delete them.
Unloading Parameter and Protection Settings
The connected Sepam™ parameter and protection setting file may only be unloaded
in Operating mode.
Once the connection has been established, use the following procedure to unload a
parameter and protection setting file:
1 Activate the "Unload Sepam™" function in the "Sepam™" menu
2 Select the file that contains the unloaded data
3 Acknowledge the end of operation report.
Local Sepam™ Operation
Connected to Sepam™, SFT2841 offers all the local operating functions available in
the advanced UMI screen, plus the following functions:
b setting of Sepam’s internal clock, via the "Sepam™ diagnosis" tab
b implementation of the disturbance recording function: enabling/disabling of
the function, retrieval of Sepam™ files, start-up of SFT2826
b consultation of the history of the last 250 Sepam™ alarms, with time-tagging
b access to Sepam™ diagnostic data, in the "Sepam™" tab box, included in
"Sepam™ diagnosis"
b in Parameter setting mode, switchgear diagnosis values may be modified:
operation counter and cumulative breaking current to reset the values after
a breaking device is changed
CAUTION
RISK OF UNINTENDED OPERATION
b Only qualified personnel should configure
and set this device in accordance with the
protection system study performed prior to
installation.
b During installation, commissioning, and
following any modification, check Sepam’s
configuration and protection function
settings for consistency with the results of
this study.
Failure to follow these instructions can result
in equipment damage.
Operating Procedure:
1 Create a Sepam™ file for the type of Sepam™ to
be set up. The newly created file contains the
factory settings of the Sepam™ parameters and
protection functions.
2 Modify the Sepam™ general settings and
protection function settings as required:
b all the data relating to the same function are
grouped together in the same screen
b it is advisable to enter all the parameters and
protection settings in the natural order of the
screens proposed by the guided navigation
mode
Entering Parameter and Protection Settings
The parameter and protection setting input fields are
suited to the type of value:
b choice buttons
b numerical value input fields
b dialogue box (Combo box)
The user must "Apply" or "Cancel" the new values
entered before going to the next screen. The
consistency of the new values is checked.
b an explicit message identifies inconsistent
values and specifies the allowable values
b values that have become inconsistent following a
parameter modification are adjusted to the
closest consistent value